SPECIFICATIONS 150 BHP |
|
| MODULATIC® Packaged
Once-Thru Steam Generators |
| Since 1903, the Vapor Power International
has provided a complete line of high quality Packaged Steam
Generators and Hot Oil Heaters for commercial, industrial, institutional,
and military applications worldwide. From each unit's inception
to after-sales support, our dedicated staff of engineers, service
technicians, sales and service personnel, and representatives
join forces to provide our customers with products and service
that exceed their expectations. |
| DESIGN DETAILS |
|
| General Information |
|
| Type of Boiler |
Watertube
|
| Model Series |
4742
|
| Rated Capacity |
150 BHP (1471 KW)
|
| Equivalent Evaporation |
5175 Ib/hr from and at 212°F
(2347 kg/hr from and at 100°C) Thermal
|
| Output |
5,021,000 Btu/hr (1,265,292 k cal/hr)
|
| Construction Codes |
ASME, Hartford, National Board
|
| Boiler Shell Insulation |
Mineral Wool Insulation
|
| Approx. Shipping Weight |
7200 Ibs (3266 kg)
|
| |
| Pressures psig (k Pa) |
|
Design
|
Operating
|
| 15 (103) |
5 - 13 (34 - 90) |
| 300 (2068) |
75 - 250 (517 -1724) |
| 600 (4137) |
200 - 540 (1379 - 3723) |
| 900 (6205) |
400 - 810 (2758 - 5585) |
| |
|
Controls
|
|
| Steam Pressure, Low Water Cutoff,
Flame Failure Protection, Coil Temperature Limit. |
| |
|
| Burner |
|
Manufacturer
|
Vapor Power International
|
| Fuels |
Light or Heavy Oil, Gas or Combination
|
Type (oil)
|
Air Atomized
|
| Type (gas) |
Multiple Orifice Nozzle
|
Fuel Specifications:
|
|
| Oil (No.2 CSG) |
141,000 Btu/U.S. gal (9386 k cal/liter)
|
| Gas |
1000 Btu/cu ft (8899 k cal/m3)
|
| Main Burner |
1 psig (6.9 k Pa)
|
Pilot Burner
|
4" w.C. (1.0 kPa)
|
Atomizing Air Requirements:
|
10 scfm @ 70 psig (0.3 m3/min
@ 483 k Pa)
|
| Ignition Type: |
|
| Oil and Gas |
Electric spark - interrupted gas pilot
|
| |
|
Power Requirements
|
|
| Main Power |
230 or 460 VAC, 3 Ph, 60 Hz
|
| Control Power |
120 VAC, 1 pH, 60 Hz
Supplied by integral transformer
|
| HP required by blower and feedwater pump: |
|
15,300psig
|
10 HP
|
| (103, 2068k Pa) |
7.5 kW
|
| 600 psig (4137 k Pa) |
15.0 HP (11.2 kW)
|
| 900 psig (6205 k Pa) |
15.0 HP (11.2 kW)
|
| |
|
| OVERALL DIMENSIONS |
|
| L x W x H |
100" x 60" x 109" (2540 mm
x 1524mm x 2769mm)
|
| Approx. Floor Loading (Wet) |
170 Ib/sq ft (832 kg/m2)
|
| |
|
| PERFORMANCE DATA |
|
| Fuel Consumption @ Rated Output |
|
| Oil |
48 gph (181.6 Iiter/hr)
|
| Gas |
6800 scfh (192.6 m3/hr)
|
| Thermal Efficiency up to 88% * |
| Turndown Ratio |
9 to 1
|
| Combustion and Ventilating Air Required: |
|
| Oil, Gas |
1318 scfm (37 m3/min)
|
| |
|
| CUSTOMER CONNECTIONS |
|
| Stack Outlet |
15" (381 mm) O.D
|
| Steam Outlet: |
|
| 15 psig (103 k Pa) |
6" x 150# ANSI
|
300 psig (2068 k Pa)
|
2" NPT
|
| 600 psig (4137 k Pa) |
2" NPT
|
900psig (6205 k Pa)
|
1 1/2" x 600# ANSI
|
Main Gas Supply
|
2 1/2" NPT
|
| Pilot Gas Supply |
3/8" NPT
|
| Oil Supply |
3/4" NPT
|
| Oil Return |
1/2" NPT
|
Atomizing Air Supply
|
1/2"NPT
|
| Feedwater lnlet (300, 600, 900 psig) |
2" NPT
|
| Feedwater Return |
3/4" NPT
|
| Blowdown Outlet,(2) |
1" NPT
|
Fill Test Valve
|
1/2" NPT
|
Water Pump Relief Valve
|
1/2" NPT
|
| Trap Return: |
|
| 15, 300, 600, 900 psig (103, 2068, 4137, 6205
k Pa) |
1" NPT
|
| Safety Valve Outlet: |
|
| 15psig(103kPa) (2) |
2 1/2" NPT
|
| 300psig (2068kPa) (2) |
2 1/2" NPT
|
| 600 psig (4137 k Pa) (2) |
2" NPT
|
| 900 psig (6205 k Pa) (2) |
1 1/4" NPT
|
Built to meet strict ASME standards, Vapor Steam Generators
are skidmounted and completely packaged; all pumps, burners and
required safety and operating devices are supplied, installed and
pre-tested at the factory.
Additionally, the advantages of our Steam Generators are:
- Fast Start-Up
- Compact Size & Low Weight
- Modulating Output
- High Pressure
- Safe Operation
Vapor Power International representatives and agents
are located worldwide. Refer to "Boilers" in the yellow
pages for the representative nearest you, or call us for further
information.
* Oil fired unit with optional stack economizer, up to 89% efficiency
using the LHv.
Specifications subject to change without notice.
|