SPECIFICATIONS 350 BHP |
|
| CIRCULATIC® Packaged
Re-Circulating Steam Generators |
| Since 1903, the Vapor Power International
has provided a complete line of high quality Packaged Steam
Generators and Hot Oil Heaters for commercial, industrial, institutional,
and military applications worldwide. From each unit's inception
to after-sales support, our dedicated staff of engineers, service
technicians, sales and service personnel, and representatives
join forces to provide our customers with products and service
that exceed their expectations. |
| DESIGN DETAILS |
|
| General Information |
|
| Type of Boiler |
Watertube
|
| Model Series |
5907
|
| Rated Capacity |
350 BHP (3433 KW)
|
| Equivalent Evaporation |
12,075 Ib/hr from and at 212°F
(5,477 kg/hr from and at 100°C) Thermal
|
| Output |
11,725,000 Btu/hr (2,954,700 k cal/hr)
|
| Construction Codes |
ASME, Hartford, National Board
|
| Boiler Shell Insulation |
Mineral Wool Insulation
|
| Approx. Shipping Weight |
13,000 Ibs (5897 kg)
|
| |
| Pressures psig (k Pa) |
|
Design
|
Operating
|
| 15 (103) |
3 - 13 (21 - 90) |
| 150 (1034) |
50-135 (345-931) |
| 250 (1724) |
100 - 225 (690 - 1551) |
| 275 (1896) |
100 - 250 (690 -1724) |
| 530 (3654) |
250 - 475 (1724 - 3275) |
| |
|
Controls
|
|
| Steam Pressure, Low Water Cutoff,
Flame Failure Protection, Coil Temperature Limit. |
| |
|
| Burner |
|
Manufacturer
|
Vapor Power International
|
| Fuels |
Light or Heavy Oil, Gas or Combination
|
Type (oil)
|
Air Atomized
|
| Type (gas) |
Multiple Orifice Nozzle
|
Fuel Specifications:
|
|
| Oil (No.2 CSG) |
141,000 Btu/U.S. gal (9386 k cal/liter)
|
| Gas |
1000 Btu/cu ft (8899 k cal/m3)
|
| Main Burner |
1 psig (6.9 k Pa)
|
Pilot Burner
|
6" w.C. (1.5kPa)
|
Atomizing Air Requirements:
|
|
| Oil (No.2 CSG) |
12 scfm @ 30 psig (0.34 m3/min @ 172 k Pa)
|
| Gas |
None Required
|
| Ignition Type: |
|
| Oil and Gas |
Electric spark - interrupted gas pilot
|
| |
|
Power Requirements
|
|
| Main Power |
230 or 460 VAC, 3 Ph, 60 Hz
|
| Control Power |
120 VAC, 1 Ph, 60 Hz
|
| HP required by circulating pump |
15 HP (11.2 KW)
|
HP required by blower
|
15 HP (11.2 KW)
|
| |
|
| OVERALL DIMENSIONS |
|
| L x W x H |
126" x 92" x 107" (3200mm
x 2337mm x 27181mm)
|
| Approx. Floor Loading (Wet) |
180 Ib/sq ft (840 kg/m2)
|
| |
|
| PERFORMANCE DATA |
|
Fuel Consumption @ Rated Output Oil
(No.2 CSG)
|
102.7 gph (389 liter/hr)
|
| Gas |
14,656 scfh (415 m3/hr)
|
| Thermal Efficiency up to 84% * |
| Turndown Ratios: |
|
| Oil and Combination |
8 to 1 Oil (No.2 CSG)
|
| Gas |
8 to 1
|
| Combustion and Ventilating Air Required: |
|
Oil and Gas
|
3112 scfm (88 m3/min)
|
| |
|
| CUSTOMER CONNECTIONS |
|
| Stack Outlet |
24" (610mm) O.D
|
| Steam Outlet: |
|
| 15 psig (103 k Pa) |
10" ASA
|
| 150,250, 275, 530 psig |
4" ASA
|
| (1034,1724,1896,3654 k Pa) |
4" ASA
|
Main Gas Supply
|
3" NPT
|
| Pilot Gas Supply |
3/8" NPT
|
| Oil Supply |
1" NPT
|
| Oil Return |
3/4" NPT
|
| Atomizing Air |
1/4" NPT
|
| Feedwater lnlet |
1 1/4" NPT
|
| Manual Blowdown Outlet: |
|
| 15psig (103kPa) |
2" NPT
|
| 150, 250, 275, 530 psig |
1" NPT
|
| (1034, 1724, 1896, 3654 k Pa) |
1" NPT
|
Safety Valve Outlet:
|
|
| 15 psig (103 k Pa) (2) |
3" NPT
|
| 150, 250, 275 psig (2) |
2 1/2" NPT
|
| (1034, 1724, 1896 k Pa) |
2 1/2" NPT
|
| 530 psig (3654kPa) (2) |
1 1/2" NPT
|
Built to meet strict ASME standards, Vapor Steam Generators
are skidmounted and completely packaged; all pumps, burners and
required safety and operating devices are supplied, installed and
pre-tested at the factory.
Additionally, the advantages of our Steam Generators are:
- Fast Start-Up
- Compact Size & Low Weight
- Modulating Output
- High Pressure
- Safe Operation
Vapor Power International representatives and agents
are located worldwide. Refer to "Boilers" in the yellow
pages for the representative nearest you, or call us for further
information.
* Oil fired unit with optional stack economizer, up to 89% efficiency
using the LHv.
Specifications subject to change without notice.
|